Benvenuti sulla nostra nuova piattaforma ICP DAS
Che sostituisce industrialtech.it

tM-AD5C CR ICP DAS Current IO Modules

tM-AD5C CR ICP DAS

tM-AD5C CR

5-channel Isolated Current Input Module

Quantity:

Price

€ 147,46

(VAT excluded)

€ 179,90(VAT included)

Prezzo di 1 pz. iva (22%) inclusa: € 179,90

Availability: 15 business days

SKU: 92963

Model: tM-AD5C CR

Need Help?


  • 5-channel Differential Inputs
  • Current Inputs
  • 120 VDC Overvoltage Protection
  • Resolution: 14/12 bits
  • Adjustable Sampling Rate
  • 4 kV ESD and EFT Protecton
  • 3 kV Surge Protection
  • Dual Watchdog
  • 2500 VDC Intra-module Isolation
  • Cost-effective
  • Wide Operating Temperature Range: -25 ~ +75°C

INTRODUCTION

The tM-AD5C is an analog input module that includes 5 differential analog input channels and provides a programmable input range on all analog inputs (+/- 20 mA, 0 ~ 20 mA, 4 ~ 20 mA). The sampling rate of the tM-AD5C is adjustable and is available in either fast or normal mode and It also provides 4 KV ESD protection as well as 2500 Vrms intra-module isolation.

APPLICATIONS

  • Industrial Automation
  • Industrial Machinery
  • Building Automation
  • Food and Beverage Systems
  • Semiconductor Fabrication
  • Control Systems

I/O SPECIFICATIONS

Analog Input
Input Channels: 5 Differential
Type: +/- 20mA, 0 ~ 20mA, 4 ~ 20mA
Resolution: Normal Mode: 14-bit

Fast Mode 12-bit
 
Sampling Rate: Normal Mode: 10 Hz total

 Fast Mode: 200 Hz total
 
Accuracy: Normal Mode: +/-0.1%

Fast Mode: +/-0.5%
 
Zero Drift: +/-20 μV/°C
Span Drift: +/-25 ppm/°C
Input Impedance: 125 Ω

SYSTEM SPECIFICATIONS

Communication
Interface: RS-485
Format: (N, 8, 1), (N, 8, 2), (O, 8, 1), (E, 8, 1)
Baud Rate: 1200 ~ 115200 bps
Protocol: DCON, Modbus/RTU, Modbus/ASCII
Dual Watchdog: Yes, Module (2.3 seconds), Communication (Programmable)
 
LED Indicators
Power: 1 LED as Power Indicator
 
Isolation
Intra-module Isolation, Field-to-Logic: 2500 VDC
 
EMS Protection
ESD (IEC 61000-4-2): ±4 kV Contact for Each Terminal

±8 kV Air for Random Point
 
EFT (IEC 61000-4-4): ±4 kV for Power
 
Power Requirements
Reverse Polarity Protection: Yes
Powered from Terminal Block: Yes, 10 ~ 30 VDC
Consumption: 1 W Max.
 
Mechanical
Dimensions (W x L x H): 52 mm x 98 mm x 27 mm
Installation: DIN-Rail Mounting
 
Environment
Operating Temperature: -25 °C ~ +75 °C
Storage Temperature: -30 °C ~ +75 °C
Humidity: 10 ~ 95% RH, Non-condensing

Disclaimer