PROFI-5024 CR
PROFIBUS Remote I/O Module (4-channel Isolated Analog Voltage & Current Output)
The PROFI-5024 is specially designed for the slave device of PROFIBUS DP protocol. It supports up to 4-channel isolated analog voltage/current output with 3750Vrms field to logic isolation. Users can easily to choose and configure it by using the GSD file in any PROFIBUS Configurator.
- Protocol & Hierarchy: DP-V0 Slave
- Supports Transmission Rate (kbps): 9.6, 19.2, 45.45, 93.75, 187.5, 500, 1500, 3000, 6000, 12000
- Transmission Rate Setting: detected automatically
- Address Setting: Address 0~126 set by rotary switches or SSA Telegram
- Indicators: PWR LED, RUN LED, ERR LED
- I/O modules Configuration: Configured by GSD file
- Network Isolation Protection: High Speed iCoupler
- DC Isolation Protection: 3000 VDC on PROFIBUS side
- 4KV ESD Protection: Contact for each terminal
HARDWARE SPECIFICATIONS
Hardware
CPU: 80186, 80 MHz or compatible
SRAM/Flash/EEPROM: 512 KB / 512 KB / 2 KB
Watchdog: Watchdog IC, CPU built-in
ESD Protection: 4 kV class A
PROFIBUS Interface
Controller: Siemens SPC3
Transceiver: ADI ADM2486
Connector: 9-pin female D-Sub
Baud Rate (bps): 9.6 k, 19.2 k, 45.45 k, 93.75 k, 187.5 k, 500 k, 1.5 M, 3 M, 6 M, 12 M
Transmission Distance (m): Depend on baud rate (for example, max. 1200 m at 9.6 kbps )
Isolation: 3000 VDC for DC-to-DC, 2500 Vrms for bus-to-logic
Protocol: DP-V0
UART Interface
COM: RS-232 on board (For updating firmware)Note 1.
I/0
Analog Output: 4 Channel Voltage & Current Output, Isolation Voltage:3750Vrms
Output Range: +/- 10V, 0 ~ 20mA, 4 ~ 20mA
Accuracy: +/- 0.1% of FSR for Voltage Output ; +/- 0.2% of FSR for Current Output
LED
Round LED: PWR LED, RUN LED, ERR LED
Power
Power supply: Unregulated +10 ~ +40 VDC
Protection: Power reverse polarity protection, Over-voltage brown-out protection
Power Consumption: 4W
Mechanism
Installation: DIN-Rail
Dimensions: 91 mm x 128 mm x 52 mm (W x L x H)
Environment
Operating Temp.: -25 ~ 75℃
Storage Temp.: -30 ~ 80℃
Humidity: 10~90% RH,non-condens