PM-2134-100-CAN
4 Loops 1 Phase Compact Smart Meter /CT:4pcs, 10mm(0-60A)/English /CAN bus , Modbus RTU
- True RMS energy and power parameters measurement in compact size
- Easy wiring for on-line installation
- RS-485 communication supported Modbus protocol
- Compatible with CAN specification 2.0B
- Support CAN baud-rate: 125 k, 250 k, 500 k, 1 M bps
- Wh accuracy better than 1% (PF=1)
- With wired clip-on CT (various types support input current up to 200A)
- LED pulse output
It's always difficult but crucial to the supervisors to figure out how much energy is consuming. ICP DAS brings the most powerful, cost effective, advanced Compact Power Meters, PM-213X series, to the markets.
With its high accuracy (1%, PF=1), the PM-213x series products can be applied both on low voltage primary side and/or medium/high voltage secondary side and enable the users to obtain in real time the reliable and accurate energy consumption readings from the monitored equipments while in operation. These compact size and cost effective Power Meters are equipped with revolutionary wired clip-on CT (various types support input current up to 200A) and standard Modbus communication RS-485 protocol for easy deployment. It works with input voltages ranging 10V ~ 500V, supporting a wide range of applications.
ICP DAS offers PM-213X family in a full range of Single-phase and Three-phase compact power meters for power monitoring. The products offer a rich feature set combined with easy-to-integrate communications.
Specifications
Input Voltage: 10 - 300 V
Input Current: CT Φ10 mm (60 A), CT Φ16 mm (100 A), CT Φ24 mm (200 A)
Aux Power: DC 10 - 30 V
Starting I: <0.025A
Frequency: 60/50 Hz
Wiring diagram: 1-phase 4-channel
Power Parameters Measures:
V1, V1, V2, V2
I 1, I 2, I 3, I 4
kW1, kW2, kW3, kW4
kVA1, kVA2, kVA3, kVA4
kvar1, kvar2, kvar3, kvar4
PF1, PF2, PF3, PF4
kWh1, kWh2, kWh3, kWh4
kVAh1, kVAh2, kVAh3, kVAh4
kvarh1, kvarh2, kvarh3, kvarh4
Communication:
Protocol:
Modbus-RTU
RS485, half duplex isolated
Baud Rate:9600, 19200(default), 38400
Protocol:
CAN bus
Baud Rate:125 k(default),250 k,500 k,1000 k
Protocol:
CANopen
Baud Rate: 10 k,20 k,50 k 125 k(default),250 k,500 k,800 k,1000 k
kWh Accuracy: 1%(PF=1)
Dimension: 78(L) × 35(W) × 99(H) mm
Operating Temperature: -10 °C ~ 70 °C
Installation: Rail-mounted