PROFI-5045 CR
PROFIBUS Remote I/O Module (24-channel Isolated Digital Output)
The PROFI-5045 is specially designed for the slave device of PROFIBUS DP protocol. It supports up to 24-channel isolated digital output with 3750Vrms field to logic isolation. Users can easily to choose and configure it by using the GSD file in any PROFIBUS Configurator.
- Protocol & Hierarchy: DP-V0 Slave
- Supports Transmission Rate (kbps): 9.6, 19.2, 45.45, 93.75, 187.5, 500, 1500, 3000, 6000, 12000
- Transmission Rate Setting: detected automatically
- Address Setting: 0~99 set by rotary switches
- Indicators: PWR and RUN LEDs
- I/O modules Configuration: Configured by GSD file
- Network Isolation Protection: High Speed iCoupler
- DC Isolation Protection: 3000 VDC on PROFIBUS side
- 4KV ESD Protection: Contact for each terminal
HARDWARE SPECIFICATIONS
Hardware
ESD Protection: 4 kV class A
PROFIBUS Interface
Controller: Profichip VPCLS2
Transceiver: ADI ADM2486
Connector: 9-pin female D-Sub
Baud Rate (bps): 9.6 k, 19.2 k, 45.45 k, 93.75 k, 187.5 k, 500 k, 1.5 M, 3 M, 6 M, 12 M
Transmission Distance (m): Depend on baud rate (for example, max. 1200 m at 9.6 kbps )
Isolation: 3000 VDC for DC-to-DC, 2500 Vrms for bus-to-logic
Protocol: DP-V0
LED
Round LED: PWR LED, RUN LED
Power
Power supply: Unregulated +10 ~ +40 VDC
Protection: Reverse polarity protection, Over-voltage brown-out protection
Power Consumption: 1 W
I/O
Digital Output
24 Channels (Sink), Isolated with common ground
Load Voltage: +10 ~ +40V
Maximum Load Current: 650mA w/ Short-Circuit Protection
Isolation Voltage: 3750 Vrms
Mechanism
Installation: DIN-Rail
Dimensions: 91 mm x 128 mm x 52 mm (W x L x H)
Environment
Operating Temp.: -25 ~ 75℃
Storage Temp.: -30 ~ 80℃
Humidity: 10~90% RH,non-condens