XV303 CR
4-ch Analog output, 4-ch Digital input (Wet) and 4-ch Power Relay (6A Rating Current) Expansion Board
- Multifunction (4 AO, 4 DI, 4 Relay)
- Individual Channel Configuration for Analog Output
- Jumper Selectable Voltage or Current Output
- Open Wire Detection for Current Output
- Configurable Power-on Value Settings
- 70 VDC Overvoltage Protection for Digital Input
INTRODUCTION
The XV303 is a multifunction expansion board that includes 4 Analog Output channels, 4 Digital Input channels and 4 Form A Relay Output channels. The Analog Output channels are 12-bit at +/-5 V, +/-10 V, 0 ~ +20 mA or +4 ~ +20 mA, and voltage and current outputs are jumper selectable. The XV303 also provides options for configuring power-on values for the Analog Output and Digital Output. 4 kV ESD protection and 2000 VDC intra-module isolation are also provided to enhance noise immunity capabilities in industrial environments.
I/O SPECIFICATIONS
Analog Output
Channels: 4
Type: 0 V ~ +5 V, ±5 V, 0 V ~ +10 V, ±10 V, 0 mA~ +20 mA, +4 mA ~ +20 mA (Jumper Selectable)
Resolution: 12-bit
Accuracy: ±0.1%
Voltage Ouput Capability: 10 V @ 20 mA
Current Load Resistance: 500 Ω
Power-on Value: Yes
Individual Channel Configuration: Yes
Digital Input/Counter
Input Channels: 4
Type: Dry Contact: -
Wet Contact: Sink/Source
ON Voltage Level: Dry Contact: -
Wet Contact: +3.5 ~ +50 VDC
OFF Voltage Level: Dry Contact -
Wet Contact: +1 VDC Max.
Input Impedance: 10 KΩ, 0.5 W
Counters: Channels: 4
Max. Count: 32-bit (0 ~ 4, 294, 967, 285)
Max. Input: Frequency 50 Hz
Min. Pulse: Width 10 ms
Overvoltage Protection: 70 VDC
Relay Output
Channels: 4
Type: Power Relay
Form A Relay: Contact Rating: 6 A @ 35 VDC
6 A @ 240 VAC
Min. Contact Load: 100 mA @ ≧12 V
Contact Material: Silver Cadmium Alloy
Operate Time: 5 ms (typical)
Release Time: 1 ms (typical)
Mechanical Endurance: 30 x 106 ops.
Electrical Endurance: 1 x 105 ops.
Power-on Value: Yes
SYSTEM SPECIFICATIONS
Communication
Interface: RS-232/TTL
Format: N, 8, 1
Baud Rate: 115200 bps
Protocol: Modbus/RTU
Isolation
Intra-module Isolation, Field-to-Logic: 2000 VDC
EMS Protection
ESD (IEC 61000-4-2): ±4 kV Contact for each Terminal
±8 kV Air For Random Terminal
Power
Power from Terminal Block: 5 VDC
Consumption: 2.9 W Max.
Mechanical
Dimensions (L x W x H): 82 mm x 59 mm x 13 mm
Environment
Operating Temperature: -25 to +75°C
Storage Temperature: -30 to +80°C
Humidity: 10 to 90% RH, Non-condensing