WISE-7517M-10
WISE I/O Module with 10/20-channels AI and 2-port Ethernet Switch
- Runs on browsers, no extra software tool is required.
- No more programming, Web pages provided for control logic editing.
- IF-THEN-ELSE logic rules execution ability.
- Built-in I/O (AI: 10/20 Channels)
- Support I/O Moniitoring/Control, Counter, Timer, Schedule, Email sending and CGI Command sending operations.
- Modbus TCP Protocol for SCADA System Integration.
- IEEE 802.3af-compliant Power over Ethernet (PoE).
- 2-port Ethernet Switch for Daisy-Chain Topology.
- MQTT Protocol for IT & IoT (Internet of Things) System Integration.
Introduction
WISE (Web Inside, Smart Engine) is a product series developed by ICP DAS that functions as control units for use in remote logic control and monitoring in various industrial applications. WISE offers a user-friendly and intuitive web site interface that allows users to implement IF-THEN-ELSE control logic on controllers just a few clicks away; no programming is required. With its powerful and easy-to-use features, it will minimize the learning curve, shorten time to market and dramatically reduce the labor and cost spent on system development.
WISE-7517M-10 is a module with 10-channel differential or 20-channel single-ended analog inputs. It provides programmable input range on all analog channels. Each analog channel has 240 Vrms high overvoltage protection. Each analog input can be programmed to accept voltage or current as input depending upon the position of corresponding jumper. It also has qualification for 4 kV ESD protection as well as 3000 VDC intra-module isolation. WISE-7517M-10 follows IEEE 802.3af-compliant Power over Ethernet (PoE) specification. It allows receiving power from PoE enabled network by Ethernet pairs. In additional to this, WISE-7517M-10 also has a built-in two-port Ethernet switch to implement daisy-chain topology. The cabling is much easier and total costs of cable and switch are significantly reduced.
By integrating with IF-THEN-ELSE rule engine, WISE-7517M-10 provides powerful functions such as I/O Monitoring/Control, Counter, Timer, Schedule, E-mail sending & CGI Command sending for use in various industrial applications. WISE-7517M-10 also supports Modbus TCP and MQTT protocols to make seamless integration with SCADA, IT and IoT (Internet of Things) system.
Applications
Building Automation, Factory Automation, Machine Automation, Remote Maintenance, Remote diagnosis and Testing Equipment, etc.
Hardware Specifications
Analog Input
Channels: 10 differential or 20 single-ended (Note1), software selectable
Type: ±150 mV, ±500 mV, ±1 V, ±5 V, ±10 V
±20 mA ,0 ~ 20 mA, 4 ~ 20 mA (Jumper Selectable)
Resolution: 16-bit
Sampling Rate: 10 Samples/Second (Total)
Accuracy: ±0.1 %
Zero Drift: ±20 μV/°C
Span Drift: ±25 ppm/°C
Overvoltage Protection Differential: 240 Vrms
Single-ended: 150 Vrms
Common Voltage Protection: ±200 VDC
Overcurrent Protection: Yes, 50 mA at 110 VDC
Virtual Channel to Channel Isolation: Yes, 400 VDC
Open Wire Detection for 4 ~ 20 mA: Yes
Input Impedance: Voltage: 2 MΩ (Differential), 1 MΩ (Single-ended)
Current: 125 Ω
Common Mode Rejection: 86 dB Min.
Normal Mode Rejection: 100 dB
Note1: Differential mode can be used for voltage input and current input.
Single-Ended mode can be used for voltage input only.
Communication
Ethernet Port: 2 x RJ-45, 10/100 Base-TX, Swtich Ports
PoE: Yes
Protocol: Modbus TCP, MQTT
LED Indicators
for System Running: Yes
for Ethernet Link/Act: Yes
for I/O Channel Status: Yes
for PoE Power: Yes
2-Way Isolation
I/O: 2500 VDC
EMS Protection
ESD (IEC 61000-4-2): ±4 kV Contact for Each Terminal and
±8 kV Air for Random Point
EFT (IEC 61000-4-4): ±2 kV for Power Line
Surge (IEC 61000-4-5): ±2 kV for Power Line
Power
Reverse Polarity Protection: Yes
Powered from Terminal Block: 12 ~ 48 VDC
Powered from PoE: Yes, IEEE 802.3af, Class1
Consumption: 3.7 W (Max.)
Mechanical
Dimensions (L x W x H): 120mm x 97mm x 42mm
Installation: Wall mounting
Environment
Operating Temperature: -25 °C to +75 °C
Storage Temperature: -30 °C to +80 °C
Humidity: 10 to 90% RH, non-condensing
Software Specifications
Functions
Rule Configuration Website: Access Web server on WISE controllers to edit and upload logic rules through web browser.
72 IF-THEN-ELSE Logic Rules: 3 IF conditions with AND or OR operators
3 THEN actions and 3 ELSE actions
48 Internal Registers: Hold temporary variables and read/write data
24 Timers: Delay / Timing functions.
24 Schedules: Setup prescheduled routine tasks.
24 Emails: Send Email messages to pre-set Email receivers.
24 CGI Commands: Send pre-set CGI commands.
24 Recipes: Set up THEN/ELSE action groups.
8 P2P remote modules: Set up the connection information for the remote WISE modules.
Modbus TCP Protocol: Real time control and monitoring I/O channels and system status of controllers via SCADA software.
MQTT Protocol: Real time message publish/subscribe mechanism for I/O channels and system status via IT/IoT software.
IF Conditions
AI Channel: = 、> 、< 、 ≥ 、 ≤ (value)
Internal Register: = 、> 、< 、 ≥ 、 ≤ (value)
Timer: Timeout, Not Timeout
Schedule: In Range, Out of Range
P2P: DI, AI, DI counter, DO counter, IR
Rule Status: Enable, Disable
THEN / ELSE Actions
Internal Register: Change the value
Timer: Start, Reset
Schedule: Enable, Disable
Email: Send
MQTT message: Send
CGI Commands: Send
Recipe: Execute
P2P: DO(On/Off), AO, IR
Rule Status: Enable, Disable