Benvenuti sulla nostra nuova piattaforma ICP DAS
Che sostituisce industrialtech.it

PM-3133-RCT2000P-MTCP ICP DAS new

PM-3133-RCT2000P-MTCP ICP DAS

PM-3133-RCT2000P-MTCP ICP DAS

PM-3133-RCT2000P-MTCP

Modbus TCP, 3-phase power meter, 2000A Rogowski Coil CT

Price

€ 1,04

(VAT excluded)

€ 1,27(VAT included)

Prezzo di 1 pz. iva (22%) inclusa: € 1,27

Availability: Not Available

SKU: 110733

Model: PM-3133-RCT2000P-MTCP

Need Help?


  • True RMS Power Measurements
  • Energy Analysis for 3P4W, 3P3W, 1P3W, 1P2W
  • Current Measurements Up to 2000 A
  • Voltage Measurements Up to 500 V
  • Rogowski Coil Soft CT for Easy Installation
  • W Accuracy Better than 1% (PF=1; Input Current >50A)
  • Supports RS-485, Ethernet (PoE) or CANopen Interface
  • Supports Modbus RTU, Modbus TCP or CANopen Protocol
  • Supports 2 Power Relay Output (Form A)
  • Total Harmonic Distortion (THD)

INTRODUCUION

ICP DAS brings the most powerful, cost-effective, advanced Smart Power Meters PM-3133-RCT that gives you access to real-time electric usage for three-phase power measurement. With its high accuracy (<1%, PF=1; Input Current >50A), this series can be used to both low voltage primary side and medium/high voltage secondary side and enables the users to obtain reliable and accurate energy consumption readings from the monitored equipments in real time under operation. These compact size and cost-effective power meters monitoring equipment with Rogowski Coil CT is "rope-style" Current Transformer which delivers "Easy Installation" features for large window size (55 ~ 105mm) and mechanical fl exibility for tight space.
 
It operates over a wide range of input voltages 10 ~ 500 VAC which allows universal compatibility. Also, with 2 channels relay outputs, it can be linked with sirens or lightings for alarm messages. It also supports Modbus RTU, Modbus TCP or CANopen protocols for easy integration.

SPCIFICATIONS

AC Power Measurement
Wiring: 3P4W-3CT, 3P3W-2CT, 3P3W-3CT, 1P2W-1CT, 1P3W-2CT
Measurement Voltage: 10 ~ 500 V
Measurement Current: CTØ55 mm (500 A), CTØ80 mm (1000 A), CTØ105 mm (2000 A)
Measurement Frequency: 50/60 Hz
W Accuracy: Better than 1% (PF=1; Input Current >50 A)
Power Parameter Measurement: True RMS voltage (Vrms), True RMS current (Irms), Active Power (kW), Active Energy (kWh), Apparent Power (kVA), Apparent Energy (kVAh), Reactive Power (kVAR), Reactive Energy (kVARh), Power Factor (PF), Frequency, THD
Data Update Rate: 1 Second
 
Communication
Protocol: Modbus TCP
 
Alarm Output
Power Relay: Form A (Normal Open) x 2; Relay Contact Voltage Range: 5 A @ 250 VAC (47 ~ 63Hz), 5 A @ 30 VDC
 
Power
Input Range: +12 ~ 48 VDC or PoE
Power Consumption: 2 W
 
Environment
Temperature: Operating Temperature: -20 ~ +70°C / Storage Temperature: -25 ~ +80°C
Ambient Relative Humidity: 10% ~ 90% RH, Non-condensing