Benvenuti sulla nostra nuova piattaforma ICP DAS
Che sostituisce industrialtech.it

M-6026U-32 CR ICP DAS Analog IO Modules

M-6026U-32 CR ICP DAS

M-6026U-32 CR

16-channel Universal Input and 16-channel Universal Output Module using the Modbus Protocol

Quantity:

Price

€ 456,68

(VAT excluded)

€ 557,15(VAT included)

Prezzo di 1 pz. iva (22%) inclusa: € 557,15

Availability: 15 business days

SKU: 110670

Model: M-6026U-32 CR

Need Help?


  • Universal Inputs and Universal Outputs
  • Status LED for Universal inputs and outputs
  • Integrated Design Allows You to Take Advantage of Inputs and Outputs
  • Any Universal I/O point can be configured as analog input/output, digital input or counter input
  • 100 VDC Over Voltage Protection for Universal Inputs
  • Open Wire Detection for +4 to +20 mA Outputs
  • Support Modbus RTU Protocol
  • Easy Mounting and Connection
  • Space Saving Design
  • Wide Operating Temperature Range: -25°C to +75°C

INTRODUCTION

The M-6026U-32 of distributed I/O provides a wide variety of input, output, and smart control solutions, all of which are based on a single universal hardware platform. The M-6026U-32 combines inputs and outputs, saving your time and space when both are at a premium. Since M-6032U-32 feature both inputs and outputs on the same board, retailers can reduce the space requirement for I/O boards by as much as 50%! Traditional I/O board schemes required retail operators to mount separate input and output boards within an enclosure, increasing the time and cost to mount the boards. The M-6000 I/O boards are communications devices needed to connect to the facility management system to control refrigeration, HVAC and lighting systems.

APPLICATIONS

  • Heating system in buildings
  • Ventilation system
  • Air-conditioning system
  • HVAC control, lighting control, door monitoring

I/O SPECIFICATIONS

Universal Input
Channels: 16
Type: 0 ~ 2.5V, 0 ~ 5 V, 0 ~ 10 V, 0 to 20 mA, 4 to 20 mA, Pt1000, Dry Contact Digital Input
Resolution: 16-bit
Accuracy: ±0.1% of FSR
Digital Input: On Level: Close to GND
       Off Level: OPEN
 
Over Voltage Protection: 100 VDC
 
Universal Output
Channels: 16
Type: 0 to 20 mA, 4 to 20 mA, 0 to 10 V
Resolution: 12-bit
Accuracy: ±0.2% of FSR
Voltage Output Capability: 10 V@ 20mA
Open Wire Detection for Current Output: Yes, Only 4 to 20 mA

SYSTEM SPECIFICATIONS

RS-485
Interface: RS-485 x 1
Format: N, 8, 1
Baud Rate: 1200 to 115200 bps
Protocol: Modbus/RTU
Dual Watchdog: Yes, Module (2.3 seconds), Communication (Programmable)
 
EMS Protection
ESD (IEC 61000-4-2): ±4 kV Contact for each Terminal

 ±8 kV Air for Random Point
 
Power Requirements
Power from Terminal Block: 24 VAC or 24 VDC
Fuse Protection: 1 A
Power Consumption: 14 W Max.
 
Mechanical
Dimensions (W x L x H): 240 mm x 135 mm x 65 mm
 
Environment
Operating Temperature: -25°C to +75°C
Storage Temperature: -40 to +80°C
Relative Humidity: 10 ~ 95% RH, Non-condensing

Disclaimer