M-7054PD-G CR
16-ch Isolated Universal DI/DO Module (500 mA Max.), with LED Display, using DCON and Modbus Protocols (Gray Cover)
The M-7054(P) provides 16 channels for universal Digital Input/Output, which can be selected via wire connections. The Digital Input channels are dry contact and can be used as 16-bit counters, while the Digital Output channels are sink type with short circuit protection and options for configuring power-on and safe Digital Output values.
The M-7054(P) also provides ±8 kV ESD, ±4 kV EFT and ±3 kV surge protection and 3750 VDCintra-module isolation to enhance noise protection capabilities in industrial environments.
M-7054PD CR: M-7054P with LED Display (Gray Cover) (RoHS)
- 16-channel Universal Digital Input/Output
- M-7054(D)
- 100 mA Load Current per Channel
- ±4 kV ESD Protection
- M-7054P(D)
- 500 mA Load Current per Channel with Short Circuit Protection
- ±8 kV ESD Protection
- ±3 kV Surge Protection for Power Line
- All Digital Input Channels can be used as 16-bit Counters
- ±4 kV EFT Protection
- 3750 VDC Intra-module Isolation
- Configurable Power-on Value Settings
- Configurable Safe Value Settings
- Wide Operating Temperature Range: -25 to +75°C
Universal Digital Input/Output
Channels: 16-channel Isolated Universal Digital Input/Output (Configurable via Wire Connection)
Digital Input:
- Dry Contact:
- ON Voltage Level: Close to GND
- OFF Voltage Level: Open
Counters:
- Max. Count: 16-bit (0~65535)
- Max. Input Frequency: 100 Hz
- Min. Pulse Width: 10 ms
Overvoltage Protection: ±60 VDC
Digital Output:
Output Type: Sink
Max. Load Current: 500 mA
Load Voltage: +5 ~ 50 VDC
Overvoltage Protection: 60 VDC
Overload Protection: Yes
Short Circuit Protection: Yes
Power-on Value: Yes, Programmable
Safe Value: Yes, Programmable
Communication
Interface: RS-485
RS-485 Bias Resistor: No (Usually supplied by the RS-485 Master. Alternatively, add a tM-SG4 or SG-785)
Format: N, 8, 1
Baud Rate: 1200 to 115200 bps
Protocol: Modbus RTU, DCON
Dual Watchdog: Yes, Module (1.6 Seconds), Communication (Programmable)
LED Indicator/Display
System LED Indicator: Yes, 1 as Power/Communication Indicator
I/O LED Indicator: Yes
7-Segment LED Display: -
Isolation
Intra-Module Isolation, Field-to-Logic: 3750 VDC
EMS Protection
ESD (IEC 61000-4-2):
- ±8 kV Contact for each Terminal
- ±16 kV Air for Random Point
EFT (IEC 61000-4-4): ±4 kV for Power Line
Surge (IEC 61000-4-5): ±3 kV for Power Line
Power
Reverse Polarity Protection: Yes
Input Range: +10 ~ +30 VDC
Consumption: 1.3 W
Mechanical
Dimensions (L x W x H): 123 mm x 72 mm x 35 mm
Installation: DIN-Rail or Wall Mounting
Environment
Operating Temperature: -25 to +75°C
Storage Temperature: -40 to +85°C
Humidity: 10 to 95% RH, Non-condensing