M-7017RMS-G CR
8-ch True RMS Input Module using DCON and Modbus Protocols (Gray Cover)
The M-7017RMS is an 8-channel differential AC input module that is used to convert the AC input signals to their True RMS DC values. The RMS input range can be from +150 mVrms to +10 Vrms, and each channel can be configured individually. The M-7017RMS is a complete, high-accuracy, RMS-to-DC converter that computes the True RMS DC value of any complex waveform. It also features 4 kV ESD protection, 2500 VDC intra-module isolation and +/-35 VDC overvoltage protection.
M-7017RMS-G CR: 8-channel True RMS Input Module (Gray Cover) (RoHS)
- 8-channel True RMS Input
- +/-0.15% Factory Calibrated Accuracy
- The RMS input range can be from +150 mVrms to + 10 Vrms
- Designed for Standard Operation with Frquencies of 45 Hz
- Individual Channel Configurable
- 4 kV ESD Protection
- +/- 35 VDC Overvoltage Protection
- 2500 VDC Intra-module Isolation
- RoHS Compliant
- Wide Operating Temperature Range: - 25 to + 75 °C
Analog Input
Channels: 8
Wiring: Differential
Input Range: 0 ~ +10 Vrms, 0 ~ +5 Vrms, 0 ~ +1 Vrms, 0 ~ +500 mVrms, 0 ~ +150 mVrms
Resolution: 16-bit
Accuracy:
- Sinusoid: 50/60 Hz = ±0.15% of FSR - 45 Hz to 10 kHz = ±0.5% of FSR
- Non-Sinusoid: Crest Factor = 1 to 2 = ±0.2% of FSR - Crest Factor = 2 to 3: ±0.35% of FSR
- DC: 0 ~ +10 Vrms/ 0 ~ +5 Vrms/ 0 ~ +1 Vrms, = ±0.3% of FSR
- Other: ±0.7% of FSR
Sampling Rate: 10 Hx (Total)
-3dB Bandwidth: 15.7 Hz
Zero Drift: ±20 μV/°C
Span Drift: ±25 ppm/°C
Common Mode Rejection: 86 dB
Normal Mode Rejection: 100 dB
Input Impedance: >2 MΩ
Individual Channel Configuration: Yes
Overvoltage Protection: +/-35 VDC
Communication
Interface: RS-485
Bias Resistor: No (Usually supplied by the RS-485 Master. Alternatively, add a tM-SG4 or SG-785)
Baud Rate: 1200 to 115200 bps
Protocol: Modbus RTU, DCON
Dual Watchdog: Yes, Module (1.6 Seconds), Communication (Programmable)
LED Indicators/Display
System LED Indicator: Yes, 1 as Power/Communication Indicator
I/O LED Indicators: --
7-segment LED Display: --
Isolation
Intra-module Isolation, Filed-to-Logic: 2500 VDC
EMS Protection
ESD (IEC 61000-4-2): ±4 kV Contact for each Terminal - ±8 kV Air for Random Point
EFT (IEC 61000-4-4): ±4 kV for Power Line
Surge (IEC 6100-4-5): ±0.5 kV for Power Line
Power
Reverse Polarity Protection: Yes
Input: +10 ~ +30 VDC
Consumption: 0.9 W
Mechanical
Dimension (L x W x H): 123 mm x 72 mm x 35 mm
Installation: DIN-Rail
Environment
Operating Temp.: -25 to + 75°C
Storage Temp.: -40 to +85 °C
Humidity: 10 to 95% RH, non-condensing